#Profibus_DP ; ; Sierra Instruments Inc. ; ; Version 1.0 ; ; This GSD-File is intended for the Smart Meter 640S ; This Unit supports DPV0 ; ; Outgoing Cyclic data (slave to master) ; ; Instance ID | Description | Size (bytes) | Format ;---------------+-----------------------+---------------+------- ; 1 | Flow | 4 | REAL ; 2 | Totalizer | 4 | REAL ; 3 | User full scale | 4 | REAL ; 4 | Factory full scale | 4 | REAL ; 5 | K-factor | 4 | REAL ; 6 | Serial Number | 12 | ASCII ; 7 | Flow unit | 5 | ASCII ; 8 | Totalizer unit | 3 | ASCII ; 9 | Status | 2 | INT ; ; Incoming Cyclic data (master to slave) ; ; Instance ID | Description | Size (bytes) | Format ;---------------+-----------------------+---------------+------- ; 10 | Reset totalizer | 4 | REAL ; 11 | User full scale | 4 | REAL ; 12 | K-factor | 4 | REAL ; GSD_Revision = 4 ; Vendor_Name = "Sierra Instruments, Inc." Model_Name = "Smart Meter 640S - Profibus" Revision = "V1.0" Ident_Number = 0x0e13 Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release = "Revision H" Software_Release = "V6.0" ; 9.6_supp = 1 19.2_supp = 1 45.45_supp = 1 93.75_supp = 1 187.5_supp = 1 500_supp = 1 1.5M_supp = 1 3M_supp = 1 6M_supp = 1 12M_supp = 1 ; MaxTsdr_9.6 = 60 MaxTsdr_19.2 = 60 MaxTsdr_45.45 = 60 MaxTsdr_93.75 = 60 MaxTsdr_187.5 = 60 MaxTsdr_500 = 100 MaxTsdr_1.5M = 150 MaxTsdr_3M = 250 MaxTsdr_6M = 450 MaxTsdr_12M = 800 ; Redundancy = 0 Implementation_Type = "VPC3+C" Bitmap_Device = "640S_De" Bitmap_Diag = "640S_Di" Bitmap_SF = "640S_Sf" ; Freeze_Mode_supp = 1 Sync_Mode_supp = 1 Auto_Baud_supp = 1 Set_Slave_Add_supp = 1 Min_Slave_Intervall = 1 ; Modular_Station = 0 ; Fail_Safe = 0 Slave_Family = 0 ; General Max_Diag_Data_Len = 6 ; DPV1_Slave = 1 C1_Read_Write_supp = 0 Max_Initiate_PDU_Length = 52 C2_Read_Write_supp = 1 C2_Max_Data_Len = 80 C2_Response_Timeout = 300 C2_Read_Write_required = 1 C2_Max_Count_Channels = 2 ; DPV1_Data_Types = 0 ; Max_User_Prm_Data_Len = 0 ; ; Module = "42 bytes in, 12 bytes out" 0xc0,0x8b,0xa9 1 EndModule